SUBSTATION SERVICE
OPERATING INSTRUCTIONS FOR SWITCHES
1. Knowledge of this manual is mandatory for:
- Head, foreman of the PS and CRO group.
- Operational and operational - production personnel of PS groups.
- Production personnel of the PS and CRO group.
The instruction was drawn up on the basis of the current "Rules for the technical operation of power plants and networks", "Rules for the installation of electrical installations", " Technical description and operating instructions for VK-10 circuit breakers.
2. General instructions. Criteria and aisles of a safe state.
2.1. High-voltage three-pole VK-10 series switches with a spring drive are designed for operation in switchgear cabinets (KRU) for indoor and outdoor installation with a rated voltage of up to 11 kV three-phase alternating current with a frequency of 50 or 60 Hz.
2.2. The circuit breaker is designed to operate under the following conditions:
- altitude up to 1000 m;
- the upper operating and effective value of the temperature of the air surrounding the circuit breaker is 45 °C, respectively.
- the lower operating temperature of the ambient air switch is minus 25 °C. To ensure the possibility of circuit breaker operation at temperatures below minus 25 °C, heating devices must be provided in the installations that provide heating of the air surrounding the circuit breaker not lower than the above for the entire time of circuit breaker operation;
- average monthly value of relative humidity - 80% at a temperature of 20 °C;
- the environment is explosion and fireproof, the content of dust and gases should not exceed the norms for atmosphere type II in accordance with GOST 15150-69.
2.3. The working position of the switch in space is vertical.
3. Basic technical data of the circuit breaker.
Table number 1.
Rated voltage, kV | 10 |
Maximum operating voltage, kV | 12 |
Rated current, A | 630; 1000; 1600* |
Rated breaking current, kA | 20; 31,5* |
Limit through current (peak value), kA | 52; 80 |
Own shutdown time, s, no more | 0,05 |
Tripping time of the circuit breaker with a drive, s, no more | 0,07 |
Rated voltage of closing and opening electromagnets: - direct current - alternating current |
24; 48; 110; 220 100; 127; 220; 380 |
Actuation current of the tripping electromagnet, A | 3; 5 |
Response voltage of control electromagnets as a percentage of the nominal: - inclusions - shutdowns |
80 - 110 % 65 - 120 % |
Rated motor voltage for winding springs - direct current, V - alternating current, V |
110; 220 127, 220 |
Working spring winding time, s, no more | 15 |
Circuit breaker weight, kg | 160 - 200 |
Oil mass, kg | 12 |
continuation of table No. 1.
VK-10High-voltage three-pole VK-10 series circuit breakers with a spring drive are designed for operation in switchgear cabinets for indoor and outdoor installation with a rated voltage up to 11 kV, 3-phase alternating current, frequency 50 or 60 Hz.
Permissible temperature range of the air surrounding the switch is from "-25" to "+45". To ensure the possibility of operation of the circuit breaker at temperatures below "-25C", heating devices must be provided in the installations.
The oil circuit breaker is controlled remotely or manually by a motor spring drive of indirect action. Switching on of the MV is carried out due to the energy previously stored by the closing springs of the drive, switching off - due to the energy stored by the opening spring oil switch when turned on.
The base of the oil circuit breaker consists of a frame on which side racks are installed for mounting the drive and a pedal is fixed to unlock the MV in the switchgear box, a grounding contact and a pole mechanism housing. The body of the pole mechanism is made as a monoblock for all three poles.
The pole of the oil circuit breaker consists of an insulating cylinder, at the lower end of which a metal flange is reinforced. Cylinders VK-10 are fixed on the mechanism body.
A current-collecting device is installed in the pole cylinder, which consists of a holder with two guide rods.
Between the guide and movable rods there is a current conductor (roller current collector), which serves to transfer current from the movable to the guide rods and at the same time to guide the movable rods. The conductor can have from four to eight pairs of rollers, depending on Inom. off
An arc chute of transverse oil blast is installed above the current collector on a spacer cylinder. A socket contact is installed above the camera. On the basis of the contact, 9 lamellas are installed in the holder - an oil circuit breaker at Inom.=630, 1000A, and 11 lamellas - MV at Inom.=1250, 1600A. The lower ends of the lamellas are lined with arc-resistant ceramic-metal.
1 - detachable contact of the retractable element;
2 - bogie frame;
3 - drive;
4 - switch pole;
5 - facade partition;
6 - plug connector;
7 - insulating casing Switch pole for 630 and 1000 A:
1 - oil indicator;
2 - guide rod;
3 - down conductor;
4 - movable rod;
5 - current-carrying rod;
6 - housing of the drive mechanism;
7 - gasket;
8 - flange;
9 - insulating rod;
10 - clip;
11 and 13 - gaskets;
12 - sleeve;
14 - spacer cylinder;
15 - arc chute;
16 - insulating cylinder;
17 - nut;
18 - contact of the retractable element;
19 - socket contact;
20 - screw;
21 - gasket;
22 - washer Switch pole VK - 10 - 31, 5 / 3150U2; VKE - 10 - 31, 5/3150U2:
1 - mechanism body;
2 - external mechanism lever;
3, 24 - gaskets;
4, 5 - insulating rods;
6, 11 - lower and upper cylinders;
7, 14 - lower and upper plates;
8 - conductor;
9, 10 - movable rods;
12 - fixed contact;
13 - movable contact of the switchgear retractable element;
15 - socket contact;
16 - oil indicator glass;
17 - clip;
18 - body;
19 - down conductor;
20, 21 - guide rods;
22 - roller;
23 - arc chute;
25 - spacer cylinder;
26, 27 - flanges;
28 — mechanism lever internal
Permissible number of short circuit interruptions PS switches:
VKE - 10 - 20 outages
TDC - 110 - 100 trips.
TDC - 220 - 400 trips (total current not more than 200 kA)
For all TDC switches, the permissible number of closing operations for short-circuit currents. is 50% of the allowed number of trip operations.
LTB 145 D1/B, LTB245 E1 - n x I = 20000, where
n is the number of current interruptions,
I - the magnitude of the short circuit current, kA.
Switch drives.
a) VKE circuit breakers are equipped with PEV-11 type electromagnetic drives.
The drive consists of a switching electromagnet (a coil, a movable core with a rod and a magnetic circuit) and a drive mechanism coupled to the switch shaft. A disconnecting electromagnet mounted on the bottom plate of the mechanism body.
The drive is equipped with an electrical interlock against spontaneous reclosing of the short circuit breaker. (jumping). The control circuits for the circuit breaker and the circuit breaker opening are connected through auxiliary contacts KBV and KBO, respectively, which ensures automatic power cut of the switching and disconnecting electromagnets after the completion of the corresponding operation.
Automata are installed in the power circuit in each cell. KMV contactors are also installed in the electromagnet circuit, which supply a rectified current to the closing coil with their contacts.
b) The VMT-110 and VMT-220 circuit breakers are equipped with spring-motor drives PprK-1400.
The drive is designed for remote (on duty) or by means of automation and local (on duty) control of the circuit breaker.
The drive ensures that the circuit breaker is closed, held in the closed position and the moving parts of the circuit breaker are released to open it. The main components of the drive are: housing, working springs, coupling and disengaging device, electromagnets for switching on and off, blocking device, electric motor with a gearbox.
The working spring winding mechanism (electric motor with worm gear and chain drive) is equipped with a spring state indicator. A handle for manual winding of springs can be installed on the shaft of the worm gearbox.
On the front side of the drive there is a panel in the form of a plate on which are installed: an automatic machine, a magnetic starter, a push-button control post, a switch for electric motor control modes (manual and automatic), and an operation counter.
On the bottom of the cabinet there are two heating devices with a power of 400 W each.
The normal position of the mode switch on the panel, in the drive cabinet is “automatic”. "Manual" is used for repair work.
The circuit breaker is controlled remotely from the control room, the key is installed on the control panel of the VMT-110 circuit breaker. If it is necessary to turn off the circuit breaker on site (with the permission of the ODS), press the button installed on the opening solenoid.
The drive has a number of interlocks:
a) against turning on the electric motor of the working spring plant when the manual winding handle is installed on the gearbox shaft (the starter circuit opens;
b) against turning on or unprepared for this operation, the mechanism of working springs, is provided by breaking the power supply circuit of the closing electromagnet.
c) against switching on “idle” (the switch is on).
The position of the switch can be judged by the index, which is located on the frame behind the glass at the first column from the drive. Enabled - "B", disabled - "O".
Possible malfunctions and ways to eliminate them.
✓15 years in the market for the manufacture of stainless steel products
Railings and railings made of stainless steel are the most popular, inexpensive and practical option for stairs. Despite their low cost, they carry their intended purpose, providing safety, convenience during ascent and descent. They are widely used in buildings for various purposes from office centers to private apartments, private houses and administrative premises.
FOKS is a diversified commercial enterprise. We are a company with a strong manufacturing base, which has more than 10 years of experience in turnkey design and installation, manufacture and sale of high quality stainless steel and balcony railings, balcony stair railings, a wide range of metal architectural and interior components.
The range of services provided by FOX to its customers includes: design, design, installation and installation of metal fences. The company also manufactures and sells components for railings, fences and thematic structures.
Only we offer real Italian stainless steel railings, which give the stairs a special charm, durability, strength and aesthetics. They are perfectly combined with stone and wooden steps. Naturally, the railing for stairs should first of all fulfill the function assigned to them, and only then shine with their beauty, but practicality in combination with aesthetics will be the best option for modern railings. And if the task is to decorate the main entrance, then the stair railings produced by the FOX company will do their job.
The company specializes and manufactures stair railings in Kyiv, stainless steel handrails, stainless steel (stainless steel) railings, combined railings for balconies, pools, stairs, atriums, ramps. Also, our company is engaged in the manufacture of such structures as: canopies, canopies, columns and many other options for configuring products from stainless steel and other metals. The team of our company employs qualified specialists with many years of experience in this field. The main goal was determined at the time of the company's creation - the production and sale of products that create a sense of security and comfort, convenience and dynamism, of the highest quality.
Our company offers customers strong, reliable and beautiful railings, stainless steel stairs, balconies, which are installed in multi-storey buildings and bunk apartments, hotels, schools, universities. Balcony railings, roof railings (roofs) finished with glass or plastic, glass holders, stainless steel canopies and awnings, external and internal glass railings. The doors of our company are open to every client!
The energy industry has a very big problem on its hands: professionals born between the mid-1940s and mid-1960s are approaching retirement age. And a very big question arises: who will replace them?
Overcoming barriers to renewable energy
Despite certain achievements in last years, energy from renewable sources is a very modest part of modern energy services around the world. Why is it so?
Real-time power transmission monitoring
Demand for electricity continues to grow and transmission companies are faced with the challenge of increasing the transmission capacity of their networks. It can be solved by building new and modernizing old lines. But there is another way to solve it, it is to use sensors and network monitoring technology.
Material capable of making solar power 'surprisingly cheap'
Solar cells, made from a material that has long been known and cheaper than silicon, can generate the same amount electrical energy like solar panels in use today.
Comparison of SF6 and vacuum circuit breakers for medium voltage
Experience in the development of medium voltage circuit breakers, both SF6 and vacuum, has provided sufficient evidence that neither of the two technologies is, in general, significantly superior to the other. Decision making in favor of one technology or another is stimulated by economic forces, user preferences, national "traditions", competencies and special requirements.
Medium voltage switchgear and LSC
Metal-encased medium voltage switchgear and loss of service (LSC) categories - categories, classification, examples.
What factors will affect the future of transformer manufacturers?
Whether you are generating or selling electricity, or supplying power transformers outside of the country, you have to fight competition in global market. There are three main categories of factors that will influence the future of all transformer manufacturers.
The future of medium voltage switching equipment
Smart grids seek to optimize the links between electricity demand and supply. By integrating more distributed and renewable energy sources into one grid. Is MV switchgear ready for these challenges, or does it need to be further developed?
In search of a replacement for SF6 gas
SF6, which has a number of useful characteristics, is used in various industries, in particular, it is actively used in the high voltage electricity sector. However, SF6 also has a significant drawback - it is a powerful greenhouse gas. It is included in the list of six gases included in the Kyoto Protocol.
Advantages and types of switchgear
It is desirable to place the electrical substation in the center of the load. However, often the main obstacle to such substation placement is the space required for it. This problem can be solved by applying GIS technology.
Vacuum as arc quenching medium
At present, at medium voltages, the technology of arc quenching in vacuum dominates over technologies using air, SF6, or oil. Generally, vacuum circuit breakers are safer, and more reliable in situations where the number of normal operations and maintenance operations short circuits, very large.
Choosing a company and planning a thermal imaging survey
If the idea of thermal imaging inspection of electrical equipment is new to you, then planning, finding a performer, and determining the benefits that this technology can bring is confusing.
The most well-known methods of isolating high voltage
The seven most common and well-known materials used as high-voltage insulation in electrical structures are given. They indicate aspects requiring special attention.
Five Technologies for Increasing the Efficiency of Electricity Transmission and Distribution Systems
When looking at the measures that have the highest potential for improving energy efficiency, transmission inevitably comes first.
Self-healing networks come to Holland
Economic growth and population growth lead to an increase in demand for electricity, along with severe restrictions on the quality and reliability of energy supplies, efforts to ensure the integrity of the network are growing. In the event of network failure, their owners are faced with the task of minimizing the consequences of these failures, reducing the time of failure, and the number of consumers disconnected from the network.
High-voltage circuit breaker equipment for each company involves a significant investment. When the question arises of their maintenance or replacement, it is necessary to consider all possible options.
Ways to develop safe, reliable and efficient industrial substations
The main factors that should be taken into account when developing electrical substations for supplying industrial consumers are considered. Attention is drawn to some innovative technologies that can improve the reliability and efficiency of substations.
To compare the use of vacuum circuit breakers or contactors with fuses in 6...20 kV distribution networks, it is necessary to understand the basic characteristics of each of these switching technologies.
AC generator breakers
Playing an important role in the protection of power plants, generator circuit breakers enable more flexible operation and provide effective solutions to reduce investment costs.
A look through switching equipment
X-ray inspection can help save time and money by reducing the amount of work. In addition, the time of disruptions in deliveries and equipment downtime at the client is also reduced.
Thermal imaging inspection of electrical substations
SF6 in the power industry and its alternatives
In recent years, security issues environment gained a lot of weight in society. SF6 emissions from switchgear are a major contributor to climate change.
hybrid switch
High-voltage circuit breakers are important electrical equipment used in power transmission networks to isolate a faulty section from a working part of the electrical network. This ensures safe work electrical system. This article analyzes the advantages and disadvantages of these two types of circuit breakers and the need for a hybrid model.
Safety and environmental friendliness of switchgear insulation
The purpose of this article is to highlight the potential dangers to personnel and the environment associated with the same equipment, but not energized. The article focuses on switching and distribution equipment for voltages above 1000 V.
Functions and design of medium and high voltage circuit breakers
Advantages of DC in high voltage lines
Despite the greater distribution of alternating current in the transmission of electrical energy, in some cases the use of high voltage direct current is preferable.